State of California Business, Consumer Services and Housing Agency Department of Housing and Community Development Division of Codes and Standards Mobilehome and Special Occupancy Parks Program
PRIVATE FIRE HYDRANT TEST AND CERTIFICATION REPORT
All parks must return this form to the enforcement agency for the park.
Part 1. IDENTIFICATIONâPARK AND PARK OPERATOR
| Park Name Park | ID# |
|---|---|
| Park Address | |
| City | CA Zip |
| Park Operator Name | |
| Park Operator Address | |
| Telephone |
Part 2. CERTIFICATION EXCEPTIONS
If any of the following appliesâyou do not need certification, but you must complete this section.
â Hydrants are publicly owned and maintained. Water Company Name___
â No hydrants AND park was built before September 1, 1968. Date of Construction ___
â No hydrants AND park has 14 or less total lots. Number of lots ___
â No private hydrants AND park was built after September 1, 1968. (Specific exception at time of construction.)
Part 3. ANNUAL FIRE HYDRANT OPERATION TEST
To be completed by authorized Certifier ONLY. Standpipes are considered hydrants for certification requirements.
Certifier: Initial your verification in the appropriate column.
| CERTIFICATIONS | YES | NO | CORRECTED & PASSED |
|---|---|---|---|
| 1. Hydrant stems and valves operate fully, freely, and are properly lubricated. | |||
| 2. All hydrant threads and caps are undamaged. | |||
| 3. Where subject to vehicular damage, hydrants are physically protected. | |||
| 4. Area around all hydrants has a minimum of 36 inches of unobstructed access. | |||
| 5. All hydrant outlets are 14 inches to 24 inches above grade. (Standpipe outlets need not be a specific height, but must be readily accessible.) | |||
| 6. Each hydrant is clearly identified or marked. | |||
| 7. Each 11/2-inch hydrant has an approved hose in a marked enclosure. |
All NO answers are violations and will prohibit the issuance of the park's Permit to Operate.
Verification:
I verify under penalty of perjury that either this park is exempt ___ from testing requirements or the hydrant operation is in compliance. Park owner or operator
Part 4. FIVE-YEAR FIRE HYDRANT WATER FLOW TEST
| Hydrant Number | Barrel Size (inches) | Flow (GPM) | Pressure (PSI) |
|---|---|---|---|
| 1 | |||
| 2 | |||
| 3 |
| Hydrant Number | Barrel Size (inches) | Flow (GPM) | Pressure (PSI) |
|---|---|---|---|
| 4 | |||
| 5 | |||
| 6 |
For more than 6 hydrants in the park, attach an additional list using the format above. (GPM=gallons per minute, PSI=residual pressure in pounds per square inch)
Part 5. CERTIFICATION OF TEST RESULTS
Certifier Name ___ License Class and No. ___
Telephone ___ Email ___
Printed Name___ Title___
Signature_____ Date of Certification_____
Part 6. APPROVAL FOR CONTINUED USE OF EXISTING SYSTEMâCOMPLETED BY LOCAL FIRE AGENCY ONLY
Agent Name ___ Title ___
Badge Number Signature
HCD MP 532 (Rev. 10/25)
INSTRUCTIONS Submit this form by email to: ParksPTO@hcd.ca.gov or by mail to: HCDâMobilehome Parks Program P.O. Box 278180 Sacramento, CA 95827-8180
HCDâMobilehome Parks ProgramP.O. Box 278180Sacramento, CA 95827-8180
Part 1. IDENTIFICATIONâPARK AND PARK OPERATOR
Park Name and Park ID #: Enter the name of the park and park identification number as shown on the Permit to Operate.
Park Address: Enter the physical address of the park.
Park Operator: Enter the name, address, telephone number, and email address of the park operator.
Part 2. CERTIFICATION EXCEPTIONS
These certificate requirements do not apply to:
- Parks with public hydrants where the local water district owns the water or hydrant system and performs regular hydrant testing. List the name of the water company.
- Parks without hydrants constructed prior to September 1, 1968.
- Parks without hydrants with 14 or less total spaces.
- Parks without hydrants constructed after September 1, 1968.
All parks with hydrants must have them tested and certified regardless of park size or date of construction.
IF ANY OF THESE EXCEPTIONS APPLY TO YOUR PARK, YOU DO NOT NEED TO COMPLETE PARTS 3-5.
Part 3. ANNUAL FIRE HYDRANT OPERATION TEST*
Initial the appropriate column to indicate where the hydrant(s):
- Stems and valves fully operate, open and close freely, and have the proper lubrication.
- Caps, seals, and threads are undamaged.
- Are provided physical protection if subject to vehicular damage.
- Has a minimum of 36 inches of clear space around hydrant(s).
- Outlets are between 14 and 24 inches above grade. Standpipe outlets need not be a specific height but must be readily accessible.
- Is clearly identified or marked for easy location in an emergency.
- That are 1 1/2 inch, have a 75-foot hose on a rack, or reel contained in an enclosed cabinet marked "FIRE HOSE" in 4-inch contrasting letters.
THE PARK OWNER/OPERATOR'S SIGNATURE VERIFYING AN EXCEPTION IS REQUIRED IN PART 3.
Part 4. FIVE-YEAR FIRE HYDRANT WATER FLOW TEST* â to ONLY be completed every five years
Barrel size: Enter the barrel or riser diameter measured in inches.
Flow: Enter the measured flow in gallons per minute (GPM).
Pressure: Enter the residual pressure measure in pounds per square inch (PSI).
Part 5. CERTIFICATION OF TEST RESULTS
This section is to be completed by the fire agency responsible for fire suppression in the park, local water supplier, Licensed Fire Protection Engineer, or C-16 Fire Protection Contractor witnessing and certifying the test information. Certifier Name: Enter the name of the person, agency, or entity certifying the test results. Contractor's Classification and Number: Enter the California Contractors State License Board classification and license number or the license number for a California licensed fire protection engineer. Address: Enter the address of the person, agency, or entity certifying the test results. Telephone: Enter the telephone number of the person, agency, or entity certifying the test results. Email: Enter the email address of the person, agency, or entity certifying the test results. Printed Name: Print the name of the person certifying the test.
Title: Enter the title of the person certifying the test.
Signature: Required signature of person certifying the test.
Date: Enter the date of the certification.
Part 6. APPROVAL FOR CONTINUED USE OF EXISTING SYSTEMâCOMPLETED BY LOCAL FIRE AGENCY ONLY
This section may only be completed by a local fire agency when a private fire hydrant cannot be repaired to meet these standards, given local conditions, and the fire agency responsible for fire suppression in the park approves its continued use or use of alternative fire protection methods.
For more information, refer to California Code of Regulations, title 25, commencing with section 1300 and/or 2300.
- VIOLATIONS: If any answers in Part 3. ANNUAL FIRE HYDRANT OPERATION TEST are NO, and/or Part 4. FIVE-YEAR FIRE HYDRANT WATER FLOW TEST does NOT meet the minimum requirements, the park is in violation. The park operator/owner is responsible for correction of violations. Failure to correct violations may result in the park not being eligible to renew its annual Permit to Operate. HCD MP 532 (Rev. 10/25) Page 2