The use may utilize a closed-loop cooling system.
The use shall deploy technologies for water conservation including, not limited to, installing closed-loop or recirculation systems to reduce demands on the water supply.
If the use is served by a public water supply, the applicant shall submit documentation from the public authority certifying that the public authority will supply the water needed.
If the use is to rely upon non-public sources of water, the applicant shall provide a water feasibility study. The purpose of the study is to determine if there is an adequate supply of water for the proposed use and to estimate the impact of the use on all existing wells, groundwater, and surface waters in the vicinity. No Data Center shall be approved unless the water feasibility study demonstrates that the anticipated water supply yield is adequate for the project and that the proposed water withdrawals and discharges will not endanger or adversely affect the quantity or quality of groundwater supplies or surface waters in the vicinity. The water feasibility study shall include the following information at a minimum: ...