Tent Fire Safety Requirements
Any tent exceeding 10'x10' will require a building permit.
Inspections
- Once erected, the tent/canopy shall be inspected for code compliance and approval by a city fire inspector prior to the event.
- To schedule the inspection, call 352-357-6585. Inspections can only be accomplished Monday through Friday 8AM-5PM. The tent must be set up and ready for inspection during normal work hours only.
- Always have the permit card and plans on hand at the event.
Tents
- Tents erected for the sale of fireworks shall comply with the criteria set forth within this checklist and criteria set forth by Florida Statute 79 l.
- Tents shall be permitted only on a temporary basis.
- Tents shall be erected to cover not more than 75 percent of the premises, unless otherwise approved by the authority having jurisdiction.
Seating
- Rows of chairs must be fastened together in groups of 3-7 chairs per group.
- There must be 12" clear width of space between each row (measured from the back of one chair to the seat front of the chair in the row directly behind).
- Center or main aisle must be 42" in width and side or cross aisles must be 36" in width.
Flame Resistance
- All tent fabric shall be flame resistant.
- One of the following shall serve as evidence that the tent fabric materials have the required flame resistance:
- a.The authority having jurisdiction shall r: require a certificate or other evidence of acceptance by an organization acceptable to the authority having jurisdiction.
- b.The authority having jurisdiction shall require a report of tests made by other inspection authorities or organizations acceptable to the authority having jurisdiction.