E. Tile Ceiling:
installed in the PVC intake ductwork at each fan to provide additional air to flow into the fans. Both fans were installed 30 years ago.
- 1. The ceiling in the storage room is falling, apparently due to the lack of an attic vapor barrier and will need to be replaced.
F. Grilles and Diffusers:
G. Attic Vapor Barrier:
- The existing grilles in the storage room are damaged and falling out of the ceiling.
- Existing supply diffusers do not have dampers accessible from below the attic insulation envelope.
- Existing exhaust grilles and return grilles have noticeable dirt and debris buildup on the face of the grilles, and do not have dampers accessible from below the attic insulation envelope.
- The ventilated attic has a layer of batt insulation with a foil face between the bottom of the roof trusses. There are large gaps in the insulation, so it does not function as a vapor barrier.
H. Mechanical Room:
- Two natural draft water heaters are existing in the mechanical room. Water heater WH-1 is a 50 gallon, 40 MBH water heater that was installed in 2019.
- WH-2 is an 84 gallon, 199 MBH, propane heater converted to natural gas. This water heater is 30 years old.
- Unit heater UH-1 is a 200 MBH, natural gas unit heater that is 30 years old.
- The mechanical room has two louvers to allow for combustion air to the water heaters, unit heater, and duct furnace. These louvers total 8 square feet.
1. Emergency Generator:
- J.Live Feed Room:
- The existing emergency generator located outside the building is 30 years old.
- The Live feed room has a 4 kW electric heater in the wall that is 30 years old.
Design Criteria
A. Indoor Space Temperatures:
- Office space:
- Analysis Room:
- i.Summer: 72F db, 50% RH
- ii.Winter: 75F db
- i.Summer: 68F db, 50% RH
- B.Outdoor Air Design Conditions:
- C.All mechanical work shall be in accordance with the current version of the Kentucky Building Code and references.
- D.All electrical work shall be in accordance with the current version of the National Electric Code.
- 4
- ii.Winter: 68F db
- Summer: 95F db, 78F wb
- Winter: 3F db