225

Bend Loss Coef:0.00Default:0.00 ftDefault:0.00 ft
Bend Location:0.00 decOp Table:Op Table:
Energy Switch:EnergyRef Node:Ref Node:
Manning's N:0.0000Manning's N:0.0000
Comment: Pipe size,material, and inverts are updated based on SR 70 survey (APR2022). Entr. & Exit loss coefficients updated
Pipe Link: P-607-200UpstreamDownstream
Scenario:ExistingInvert:50.80 ftInvert:50.70 ft
From Node:607Manning's N:0.0220Manning's N:0.0220
To Node:200Geometry:CircularGeometry:Circular
Link Count:1Max Depth:1.50 ftMax Depth:1.50 ft
Flow Direction:BothBottom Clip
Damping:0.0000 ftDefault:0.00 ftDefault:0.00 ft
Length:40.00 ftOp Table:Op Table:
FHWA Code:6Ref Node:Ref Node:
Entr Loss Coef:0.20Manning's N:0.0000Manning's N:0.0000
Exit Loss Coef:1.00Top Clip
Bend Loss Coef:0.00Default:0.00 ftDefault:0.00 ft
Bend Location:0.00 decOp Table:Op Table:
Energy Switch:EnergyRef Node:Ref Node:
Comment: Field Visit: Pipe Size estimated; Inverts estimated from DEMManning's N:0.0000Manning's N:0.0000
Pipe Link: P-607-600UpstreamDownstream
Scenario:ExistingInvert:51.50 ftInvert:51.40 ft
From Node:607Manning's N:0.0220Manning's N:0.0220
To Node:600Geometry:CircularGeometry:Circular
Link Count:1Max Depth:1.50 ftMax Depth:1.50 ft
Flow Direction:BothBottom Clip
Damping:0.0000 ftDefault:0.00 ftDefault:0.00 ft
Length:40.00 ftOp Table:Op Table:
FHWA Code:4Ref Node:Ref Node:
Entr Loss Coef:0.50Manning's N:0.0000Manning's N:0.0000
Exit Loss Coef:0.00Top Clip
Bend Loss Coef:0.00Default:0.00 ftDefault:0.00 ft
Bend Location:0.00 decOp Table:Op Table:
Energy Switch:EnergyRef Node:Ref Node:
Comment: Field Visit; Pipe Size estimated; Inverts estimated from DEMManning's N:0.0000Manning's N:0.0000

Pipe Link: P-609-404 Upstream Downstream

Scenario: Existing Invert: 48.60 ft Invert: 48.50 ft