2024 Springwells Regulated Detected Contaminants Table
2024 Inorganic Chemicals - Annual Monitoring at Plant Finished Tap
Regulated ContaminantTest DateUnitHealth Goal MCLGAllowed Level MCLHighest Level DetectedRange of DetectionViolationMajor Sources in Drinking Water
Fluoride02-13-2024ppm440.49n/anoErosion of natural deposit; Water additive, which promotes strong teeth; Discharge from fertilizer and aluminum factories.
Nitrate02-13-2024ppm10100.31n/anoRunoff from fertilizer use; Leaching from septic tanks, sewage; Erosion of natural deposits.
2024 Disinfection Residual - Monitoring in the Distribution System
Regulated ContaminantTest DateUnitHealth Goal MRDLGAllowed Level MRDLHighest Level RAARange of Quarterly ResultsViolationMajor Sources in Drinking Water
Chlorine Residual2024ppm440.740.63-0.76noWater additive used to control microbes
2024 Turbidity - Monitored Every 4 Hours at the Plant Finished Water Tap
Highest Single Measurement Cannot Exceed 1 NTULowest Monthly % of Samples Meeting Turbidity Limit of 0.3 NTU (minimum 95%)ViolationMajor Sources in Drinking Water
0.13 NTU100%noSoil Runoff
Turbidity is a measure of the cloudiness of the water. We monitor it because it is a good indicator of the effectiveness of our filtration system
Summary of Violation: Great Lakes Water Authority (GLWA) did not monitor individual filter turbidity for five hours on September 2, 2024, due to an interruption of power at the GLWA Springwells Water Treatment Plant. The issue was resolved.
2024 Special Monitoring
ContaminantTest DateUnitMCLGMCLHighest Level DetectedSource of Contaminant
Sodium02-13-2024ppmn/an/a5.2Erosion of natural deposits
Regulated ContaminantTreatment TechniqueTypical Source of Contaminant
Total Organic CarbonThe Total Organic Carbon (TOC) removal ratio is calculated as the ratio between the actual TOC removal and the TOC removal requirements. The TOC is measured each quarter and because the level is low, there is no requirement for TOC removal.Erosion of natural deposits
These tables are based on tests conducted by GLWA in the year 2024 or the most recent testing done within the last five calendar years. GLWA conducts tests throughout the year only tests that show the presence of a substance or require special monitoring are presented in these tables. The State allows us to monitor for certain contaminants less than once per year because the concentrations of these contaminants are not expected to vary significantly from year to year. The data is representative of the water quality, but some are more than one year old.
About Unregulated Contaminant Monitoring
Unregulated contaminants are those for which EPA has not established drinking water standards. Monitoring helps EPA to determine where these contaminants occur and whether it needs to regulate those contaminants.
Unregulated ContaminantAverage Level DetectedRangeYear SampledComments
[Name of Unregulated Contaminant] (unit)
[Name of Unregulated Contaminant] (unit)