- DETENTION/RETENTION BASIN NOTES (continued)
- D.EMERGENCY SPILLWAY
- The spillway shall be lined with a minimum of 4-inch thick concrete, reinforced with 6" × 6" × 10/10 welded wire mesh. The concrete must extend a minimum of 3 feet down the upstream face of the embankment.
- Spillway and outlet structures may be combined into a single structure, but the low-flow outlet capability must be retained, if required by the City Engineer. Details must be included on grading plans.
- Spillway may be combined with access driveway, if approved by the City Engineer. Details must be included on grading plans.
- E.EROSION CONTROL
- Except for bottom and concrete areas, all interior surfaces of the basin shall be prepared and hydroseeded as required by the City Landscape Architect.
- There shall be no permanent landscape irrigation system inside the basin.
- CITY OF PALMDALE...
BASIN NOTES Std. No.
Approved City Engineer D-7.3