[ ] *Label and flag up (45 degrees) all inlets and outlets unless the required drop is centerline.

[] *Main sewer line or house laterals must be encased where less than four feet of cover to subbase in street is available. Ink on back of sheet.

[ ] In local streets, main line sewers should be located 5 feet northerly or easterly of the street centerline.

[ ] Minimum distance between center of manhole and curb line is 6 feet.

[ ] City boundary line to be shown as dash-double dot lines. ___

[ ] *Maximum manhole distance to be 350 feet.

[] * Horizontal curve table with delta, radius, length of curve, and tangent consecutively labeled. Horizontal curve data shall be identified by a number in a circle and shall be consistent throughout the set of plans. Only one curve of any kind allowed between manholes. Minimum radius for 8" sewer is 150 feet. Maximum delta is 60 degrees.

[ ] Call out curb lines, utilities and substructures, street centerline, H.L., wyes, encasements, cradles, chimneys, shallow manholes, stubs, plugs, BC and EC, easements, future construction, identical points, direction of flow, size of sewers, R/W.

[ ] Call out page references to match lines.

[ ] *Elevation of MH tops required in areas of new paving. MH tops in existing paving to meet grade. MH tops in undeveloped areas to be 6" above grade.

[ ] *For required drops through manholes see STD. S-C5.

[ ] For main line sewers with less than 7 feet of cover, coordinate with Sewer Maintenance.

[ ] *Review comments from Sewer Maintenance required for thorough check.