Sarasota Manatee Airport Consolidated Rental Car Facility, Quick Turnaround, and Maintenance Professional Engineering Services Proposal Page 12
Emergency Power Requirements: A separate emergency power system will be provided to serve life safety and optional stand by loads. The generator will be exterior in a sound weatherproof enclosure at exterior location and on diesel fuel tank.
Lightning Protection System: The Rental Car Quick Turn Around will be protected by a lightning protection system installed in accordance with NFPA 780. The lightning protection system shall consist of air terminals, main conductors, down conductors and ground rods. All material for the lightning protection system will be copper. Air terminals shall be spaced along the structure at a maximum interval of 20"-0" on center. The terminals shall be 12" and mounted to the structure using appropriate mounting hardware. The terminals shall be connected using main conductors. Down conductors connected to the system shall be spaced at intervals not more than 100'-0".
Lighting: direct lighting shall be used to provide the required foot-candles within the space:
Provide an average horizontal lighting level of 10-15 foot-candles at the floor level in the stacking area.
Area lighting is located directly over the islands and at the center of the drive lanes and shall maintain a minimum of 30 foot-candles @ 1'-0" above finished floor.
Waterproof light fixtures, wall-mounted along each side of the car wash bays should provide a minimum of 10 foot-candles @ 1'-0" above finished floor.
Provide an average horizontal lighting level of 50-60 foot-candles at the floor level in the maintenance bays (if applicable).
Proposed light fixtures should require minimal maintenance and be easy to maintain when required.
Lamp technology shall be LED.
General lighting shall provide appropriate color rendition for surveillance cameras.
Proposed light fixture installation shall meet requirements of the ASHRAE 90.1-10 and IECC 2012.
Conduits shall be embedded where possible.
Lighting Control: Provide lighting controls to limit energy use and with software system compliant with mechanical systems.
Emergency Lighting: Provide emergency and exit lighting as required for code