            "text": "described above, VMUS currently does not have any overhead power lines located within or near a Tier 2 or Tier 3 Fire Threat District; however, VMUS staff uses their knowledge of the specific environmental and geographical conditions of VMUS' service territory to determine if any particular areas require more frequent inspections."
        },
        {
            "id": "p12.2",
            "order": 2,
            "type": "text",
            "bbox": {
                "l": 68.64,
                "t": 666.72,
                "r": 538.32,
                "b": 630.48
            },
            "text": "If VMUS staff discovers a facility in need of repair that is owned by an entity other than VMUS, VMUS will issue a notice to repair to the facility owner and work to ensure that necessary repairs are completed promptly."
        },
        {
            "id": "p12.3",
            "order": 3,
            "type": "heading",
            "bbox": {
                "l": 126.48,
                "t": 628.08,
                "r": 258.48,
                "b": 615.36
            },
            "text": "E. RECLOSING POLICY",
            "attrs": {
                "block_label": "paragraph_title"
            },
            "level": 3
        },
        {
            "id": "p12.4",
            "order": 4,
            "type": "text",
            "bbox": {
                "l": 68.64,
                "t": 600.72,
                "r": 512.88,
                "b": 560.88
            },
            "text": "VMUS' electrical system is primarily underground and has no automatic re-closures in service. In a relayed event, re-closures will be handled on a case-by-case basis after circuit and equipment inspections have been performed. VMUS does not change substation relay settings."
        },
        {
            "id": "p12.5",
            "order": 5,
            "type": "heading",
            "bbox": {
                "l": 126.24,
                "t": 548.88,
                "r": 250.08,
                "b": 536.16
            },
            "text": "F. DE-ENERGIZATION",
            "attrs": {
                "block_label": "paragraph_title"
            },
            "level": 3
        },
        {
            "id": "p12.6",
            "order": 6,
            "type": "text",
            "bbox": {
                "l": 68.4,
                "t": 521.52,
                "r": 535.2,
                "b": 455.28
            },
            "text": "VMUS has the authority to preemptively shut off power due to fire-threat conditions; however, this option will only be used in extraordinary circumstances. Due to the minimal risk of VMUS' electrical supply facilities causing a power-line ignited wildfire, VMUS is not adopting specific protocols for de-energizing any portions of its electric distribution system. VMUS will re-evaluate this determination in future updates to this Wildfire Mitigation Plan."
        },
        {
            "id": "p12.7",
            "order": 7,
            "type": "heading",
            "bbox": {
                "l": 88.08,
                "t": 431.28,
                "r": 275.52,
                "b": 416.64
            },
            "text": "VI. RESTORATION OF SERVICE",
            "attrs": {
                "block_label": "paragraph_title"
            },
            "level": 3
        },
        {
            "id": "p12.8",
            "order": 8,
            "type": "text",
            "bbox": {
                "l": 68.4,
                "t": 401.04,
                "r": 534.24,
                "b": 348
            },
            "text": "VMUS' electric distribution system is completely underground. However, we are interconnected with SCE's transmission and distribution systems, much of which is overhead and exposed to wind, rain and lightning. This is our primary source of vulnerability to potential electrical service interruptions during rain and windstorms such as the ones that can be precipitated by El Niño."
        },
        {
            "id": "p12.9",
            "order": 9,
            "type": "text",
            "bbox": {
                "l": 68.4,
                "t": 338.64,
                "r": 531.12,
                "b": 298.56
            },
            "text": "Our underground electric distribution system is designed, and has been constructed, with redundant sources of feed. These do not guarantee the elimination of outages but can facilitate service restoration and reduce the duration of such outages."
        },
        {
            "id": "p12.10",
            "order": 10,
            "type": "text",
            "bbox": {
                "l": 68.4,
                "t": 288.96,
                "r": 536.16,
                "b": 209.28
            },
            "text": "Preparation in advance of predicted storms: Since, as discussed in the introduction, our primary trouble source during storms is outages on SCE's transmission and distribution lines, many of which are overhead, we will patrol, to the extent practical, SCE's primary interconnect lines for any potential trouble spots or vulnerabilities. We will also double check the loading conditions of our underground lines to satisfy ourselves that alternate sources have the capacity to serve the electric load (customers) in the event that it is necessary."
        },
        {
            "id": "p12.11",
            "order": 11,
            "type": "text",
            "bbox": {
                "l": 68.4,
                "t": 199.44,
                "r": 531.12,
                "b": 119.28
            },
            "text": "Our underground system will be patrolled in advance of storms for any open trenches or excavations at construction sites to minimize water intrusion into the underground system. Although the underground system is designed to operate under such conditions, small pinholes in splices or cable can cause problems, including possible electrical shorts/faults that can interrupt service to customers. Likewise, after the storm, each underground vault, manhole or other structure will be inspected for water intrusion and pumped, when necessary, in accordance proper utility practice and environmental guidelines."
        },
        {
            "id": "p12.12",
            "order": 12,
            "type": "text",
            "bbox": {
                "l": 68.4,
                "t": 110.16,
                "r": 533.04,
                "b": 69.6
            },
            "text": "All vehicular equipment, tools, and appurtenances will be thoroughly inspected for proper operation. All operating personnel will be placed on standby in the event of weather related problems. The VMUS operations and admin staff will be prepared for handling of trouble calls from customers and dispatching"
        },
        {
            "id": "p12.13",
            "order": 13,
            "type": "footer",
            "bbox": {
                "l": 62.16,
                "t": 60,
                "r": 186.96,
                "b": 37.92
            },
            "text": "VMUS Wildfire Mitigation Plan\nJune 15, 2021",
            "attrs": {
                "block_label": "footer"
            }
        },
        {
            "id": "p12.14",
            "order": 14,
            "type": "footer",
            "bbox": {
                "l": 459.12,
                "t": 48.72,
                "r": 471.6,
                "b": 38.64
            },
            "text": "10",